Exciter Model: AC6C

 

Model Equations and/or Block Diagrams

Parameters:

OEL OEL input: if = 2, LV gate; if < 2, subtract from error signal
UEL UEL input: if = 2, HV gate; if < 2, add to error signal
SCL SCL input: if = 2, LV gate; if < 2, subtract from error signal
Tr Filter time constant, sec
Ka Voltage regulator gain
Ta Voltage regulator time constant, sec
Tk Time constant, sec
Tb Time lag constant, sec
Tc Time lead constant, sec
VaMax Maximum control element output, pu
VaMin Minimum control element output, pu
Eefmax Maximum exciter field voltage, pi
Eefmin Minimum exciter field voltage, pi
Te Exciter field time constant, sec
Vfelim Model Parameters\Vfelim
Kh Exciter field current feedback gain, pu
Vhmax Model Parameters\Vhmax
Th Time lag constant, sec
Tj Time lead constant, sec
Kc Rectifier loading factor proportional to commutating reactance
Kd Exciter internal reactance, pu
Ke Exciter field resistance constant, pu
E1 Field voltage value, 1
SE1 Saturation factor at E1
E2 Field voltage value, 2
SE2 Saturation factor at E2
Vfemax Exciter field current limit parameter, pu
Vemin Minimimum exciter output voltage, pu
Spdmlt If not zero, multiply output (Efd) by generator speed